Utility · TX2120027

WRIGHT CITY WSC 1

WRIGHT CITY WSC 1 (PWSID TX2120027) is an active community water system in Texas serving about 1,350 people through roughly 450 service connections. Its primary source is listed as groundwater (wells). Cities/areas associated with this system in EPA geographic data: Arp. In recent EPA records indexed here, we found 32 violation record(s), including 23 health-based and 0 still listed as addressed/unaddressed (not fully resolved). This page summarizes public EPA SDWA/ECHO data for educational purposes. It is not a substitute for your utility’s official Consumer Confidence Report or public notices.

1,350population served
450service connections
23health-based viol.
32viol. rows indexed

System facts

  • PWSID: TX2120027
  • Type: Community water system (active)
  • Primary source: Groundwater (wells)
  • Owner type: Local government
  • Wholesaler flag: No
  • Phone (EPA record): 903-859-1281
  • Address (EPA record): PO BOX 130, Arp 75750

Service geography

Cities/areas:

Arp

Counties: Smith

ZIPs served (EPA geo): —

Recent violation records (indexed subset)

Showing up to 40 recent violation identities (2021+ when dated), deduplicated from SDWA_VIOLATIONS_ENFORCEMENT. Status meanings come from EPA’s data dictionary (Resolved / Addressed / Unaddressed / Archived).

BeginContaminant / issueViolationCategoryHealth-basedStatusResult / MCL
10/03/2022Public NoticePublic Notification Violation for NPDWR ViolationOtherNoResolved— / MCL
10/01/2025TTHMMaximum Contaminant Level Violation, AverageMCLYesArchived.182 MG/L / MCL 0.080 mg/L
10/01/2024TTHMMaximum Contaminant Level Violation, AverageMCLYesArchived.177 MG/L / MCL 0.080 mg/L
10/01/2023TTHMMaximum Contaminant Level Violation, AverageMCLYesArchived.164 MG/L / MCL 0.080 mg/L
10/01/2022TTHMMaximum Contaminant Level Violation, AverageMCLYesArchived.129 MG/L / MCL 0.080 mg/L
10/01/2021Lead and Copper RuleOCCT/SOWT Study/RecommendationTTYesResolved— / MCL TT
10/01/2021TTHMMaximum Contaminant Level Violation, AverageMCLYesArchived.147 MG/L / MCL 0.080 mg/L
07/01/2025TTHMMaximum Contaminant Level Violation, AverageMCLYesArchived.171 MG/L / MCL 0.080 mg/L
07/01/2024TTHMMaximum Contaminant Level Violation, AverageMCLYesArchived.178 MG/L / MCL 0.080 mg/L
07/01/2023TTHMMaximum Contaminant Level Violation, AverageMCLYesArchived.136 MG/L / MCL 0.080 mg/L
07/01/2022TTHMMaximum Contaminant Level Violation, AverageMCLYesArchived.143 MG/L / MCL 0.080 mg/L
07/01/2021TTHMMaximum Contaminant Level Violation, AverageMCLYesArchived.145 MG/L / MCL 0.080 mg/L
04/01/2026TTHMMaximum Contaminant Level Violation, AverageMCLYesArchived.151 MG/L / MCL 0.080 mg/L
04/01/2025TTHMMaximum Contaminant Level Violation, AverageMCLYesArchived.18 MG/L / MCL 0.080 mg/L
04/01/2024TTHMMaximum Contaminant Level Violation, AverageMCLYesArchived.165 MG/L / MCL 0.080 mg/L
04/01/2023TTHMMaximum Contaminant Level Violation, AverageMCLYesArchived.136 MG/L / MCL 0.080 mg/L
04/01/2022TTHMMaximum Contaminant Level Violation, AverageMCLYesArchived.143 MG/L / MCL 0.080 mg/L
04/01/2021TTHMMaximum Contaminant Level Violation, AverageMCLYesArchived.141 MG/L / MCL 0.080 mg/L
01/01/2026Lead and Copper RuleWater Quality Parameter M/RMRNoArchived— / MCL TT
01/01/2026TTHMMaximum Contaminant Level Violation, AverageMCLYesArchived.171 MG/L / MCL 0.080 mg/L
01/01/2025TTHMMaximum Contaminant Level Violation, AverageMCLYesArchived.171 MG/L / MCL 0.080 mg/L
01/01/2024TTHMMaximum Contaminant Level Violation, AverageMCLYesArchived.162 MG/L / MCL 0.080 mg/L
01/01/2023TTHMMaximum Contaminant Level Violation, AverageMCLYesArchived.131 MG/L / MCL 0.080 mg/L
01/01/2022TTHMMaximum Contaminant Level Violation, AverageMCLYesArchived.144 MG/L / MCL 0.080 mg/L
01/01/2022AldicarbMonitoring, RegularMRNoArchived— / MCL
01/01/2022Aldicarb sulfoneMonitoring, RegularMRNoArchived— / MCL
01/01/2022Aldicarb sulfoxideMonitoring, RegularMRNoArchived— / MCL
01/01/2022OXAMYLMonitoring, RegularMRNoArchived— / MCL 0.2 mg/L
01/01/2022Lead and Copper RuleWater Quality Parameter M/RMRNoResolved— / MCL TT
01/01/2022CarbofuranMonitoring, RegularMRNoArchived— / MCL 0.04 mg/L
01/01/2021TTHMMaximum Contaminant Level Violation, AverageMCLYesArchived.15 MG/L / MCL 0.080 mg/L
—Unspecified—No——

Lead & copper rule sample highlights

Codes PB90 / CU90 in SDWIS typically represent 90th percentile lead/copper monitoring results under the Lead and Copper Rule.

Lead (PB90)

  • 12/31/2025: 0 mg/L
  • 12/31/2024: 0 mg/L
  • 12/31/2023: 0 mg/L
  • 12/31/2022: 0 mg/L
  • 12/31/2008: .003 mg/L
  • 12/31/1999: .0043 mg/L
  • 12/31/1996: .0028 mg/L
  • 12/31/1995: .0039 mg/L

Lead explainer →

Copper (CU90)

  • 12/31/2017: 1.75 mg/L
  • 12/31/2014: 1.6 mg/L

Copper explainer →

FAQs

What does PWSID TX2120027 mean?

A Public Water System Identification number uniquely identifies a system in EPA’s Safe Drinking Water Information System (SDWIS). Texas IDs start with TX.

How current is this page?

Systems and geography reflect the EPA SDWA quarterly snapshot used for this build. Violation rows are a filtered recent subset (generally 2021+) and capped for readability—always confirm on ECHO and your CCR.

What should I do if I see a health-based violation?

Read the dates and status. Contact the utility for context, check for public notices, and review the newest Consumer Confidence Report. For medical concerns, talk with a clinician—this site is educational only.

Do lead/copper samples mean my home is safe?

LCR samples are utility monitoring results (often 90th percentile summary codes like PB90/CU90), not a test of every tap. Home plumbing can differ. Consider a certified lab test if you have reason for concern.

Citations