Utility · TX0420034
COLEMAN COUNTY SUD
COLEMAN COUNTY SUD (PWSID TX0420034) is an active community water system in Texas serving about 5,000 people through roughly 2,898 service connections. Its primary source is listed as purchased surface water. Cities/areas associated with this system in EPA geographic data: Coleman. In recent EPA records indexed here, we found 31 violation record(s), including 7 health-based and 12 still listed as addressed/unaddressed (not fully resolved). This page summarizes public EPA SDWA/ECHO data for educational purposes. It is not a substitute for your utility’s official Consumer Confidence Report or public notices.
System facts
- PWSID: TX0420034
- Type: Community water system (active)
- Primary source: Purchased surface water
- Owner type: Local government
- Wholesaler flag: No
- Phone (EPA record): 325-625-2133
- Address (EPA record): 214 SANTA ANNA AVE, Coleman 76834
Recent violation records (indexed subset)
Showing up to 40 recent violation identities (2021+ when dated), deduplicated from SDWA_VIOLATIONS_ENFORCEMENT. Status meanings come from EPA’s data dictionary (Resolved / Addressed / Unaddressed / Archived).
| Begin | Contaminant / issue | Violation | Category | Health-based | Status | Result / MCL |
|---|---|---|---|---|---|---|
| 12/27/2022 | TTHM | Failure Submit IDSE/Subpart V Plan Rpt | MR | No | Resolved | — / MCL 0.080 mg/L |
| 12/01/2024 | Lead and Copper Rule | Public Education | TT | Yes | Resolved | — / MCL TT |
| 10/17/2024 | LEAD AND COPPER RULE REVISIONS | LSL Reporting | RPT | No | Addressed | — |
| 10/17/2024 | LEAD AND COPPER RULE REVISIONS | LSL Inventory | TT | Yes | Addressed | — |
| 10/01/2025 | TTHM | Maximum Contaminant Level Violation, Average | MCL | Yes | Archived | .086 MG/L / MCL 0.080 mg/L |
| 08/23/2021 | Public Notice | Public Notification Violation for NPDWR Violation | Other | No | Resolved | — / MCL |
| 07/01/2021 | Lead and Copper Rule | Follow-up Or Routine LCR Tap M/R | MR | No | Resolved | — / MCL TT |
| 06/15/2025 | Public Notice | Public Notification Violation for NPDWR Violation | Other | No | Unaddressed | — / MCL |
| 06/12/2026 | Public Notice | Public Notification Violation for NPDWR Violation | Other | No | Unaddressed | — / MCL |
| 05/14/2026 | Public Notice | Public Notification Violation for NPDWR Violation | Other | No | Unaddressed | — / MCL |
| 05/10/2026 | TTHM | Failure Submit IDSE/Subpart V Plan Rpt | MR | No | Unaddressed | — / MCL 0.080 mg/L |
| 05/01/2025 | Public Notice | Public Notification Violation for NPDWR Violation | Other | No | Unaddressed | — / MCL |
| 04/28/2025 | Public Notice | Public Notification Violation for NPDWR Violation | Other | No | Resolved | — / MCL |
| 04/04/2025 | TTHM | Failure Submit IDSE/Subpart V Plan Rpt | MR | No | Resolved | — / MCL 0.080 mg/L |
| 04/02/2026 | Public Notice | Public Notification Violation for NPDWR Violation | Other | No | Unaddressed | — / MCL |
| 04/01/2026 | TTHM | Maximum Contaminant Level Violation, Average | MCL | Yes | Archived | .084 MG/L / MCL 0.080 mg/L |
| 04/01/2025 | Lead and Copper Rule | OCCT/SOWT Study/Recommendation | TT | Yes | Resolved | — / MCL TT |
| 04/01/2023 | Public Notice | Public Notification Violation for NPDWR Violation | Other | No | Resolved | — / MCL |
| 03/01/2026 | Revised Total Coliform Rule | Monitoring, Routine (RTCR) | MON | No | Resolved | — |
| 03/01/2022 | Revised Total Coliform Rule | Monitoring, Routine (RTCR) | MON | No | Resolved | — |
| 02/02/2026 | TTHM | Failure Submit IDSE/Subpart V Plan Rpt | MR | No | Unaddressed | — / MCL 0.080 mg/L |
| 02/02/2026 | Total Haloacetic Acids (HAA5) | Failure Submit IDSE/Subpart V Plan Rpt | MR | No | Unaddressed | — / MCL 0.060 mg/L |
| 01/19/2024 | Public Notice | Public Notification Violation for NPDWR Violation | Other | No | Resolved | — / MCL |
| 01/03/2026 | Public Notice | Public Notification Violation for NPDWR Violation | Other | No | Unaddressed | — / MCL |
| 01/01/2026 | TTHM | Failure Submit IDSE/Subpart V Plan Rpt | MR | No | Unaddressed | — / MCL 0.080 mg/L |
| 01/01/2026 | TTHM | Maximum Contaminant Level Violation, Average | MCL | Yes | Archived | .086 MG/L / MCL 0.080 mg/L |
| 01/01/2026 | Lead and Copper Rule | OCCT/SOWT Study/Recommendation | TT | Yes | Resolved | — / MCL TT |
| 01/01/2024 | Nitrate | Monitoring, Regular | MR | No | Archived | — / MCL 10 mg/L |
| 01/01/2023 | Nitrate | Monitoring, Regular | MR | No | Archived | — / MCL 10 mg/L |
| 01/01/2021 | Lead and Copper Rule | Follow-up Or Routine LCR Tap M/R | MR | No | Resolved | — / MCL TT |
| — | Unspecified | — | No | — | — |
Lead & copper rule sample highlights
Codes PB90 / CU90 in SDWIS typically represent 90th percentile lead/copper monitoring results under the Lead and Copper Rule.
Lead (PB90)
- 12/31/2025: .00289 mg/L
- 12/31/2024: .0169 mg/L
- 12/31/2023: .011 mg/L
- 12/31/2021: .00849 mg/L
- 12/31/2019: .00858 mg/L
- 12/31/2017: .0069 mg/L
- 12/31/2014: .0049 mg/L
- 12/31/2013: .00645 mg/L
FAQs
What does PWSID TX0420034 mean?
A Public Water System Identification number uniquely identifies a system in EPA’s Safe Drinking Water Information System (SDWIS). Texas IDs start with TX.
How current is this page?
Systems and geography reflect the EPA SDWA quarterly snapshot used for this build. Violation rows are a filtered recent subset (generally 2021+) and capped for readability—always confirm on ECHO and your CCR.
What should I do if I see a health-based violation?
Read the dates and status. Contact the utility for context, check for public notices, and review the newest Consumer Confidence Report. For medical concerns, talk with a clinician—this site is educational only.
Do lead/copper samples mean my home is safe?
LCR samples are utility monitoring results (often 90th percentile summary codes like PB90/CU90), not a test of every tap. Home plumbing can differ. Consider a certified lab test if you have reason for concern.
Citations
- EPA SDWIS via ECHO SDWA downloads: systems, geographic areas, violations/enforcement, LCR samples — SDWA Data Download Summary
- Explore the system in EPA tools using PWSID
TX0420034— ECHO home - Learn more about standards: EPA Safe Drinking Water Act