Utility · TX0730002
CITY OF MARLIN
CITY OF MARLIN (PWSID TX0730002) is an active community water system in Texas serving about 5,516 people through roughly 2,865 service connections. Its primary source is listed as surface water (lakes/rivers). Cities/areas associated with this system in EPA geographic data: Marlin. In recent EPA records indexed here, we found 38 violation record(s), including 17 health-based and 13 still listed as addressed/unaddressed (not fully resolved). This page summarizes public EPA SDWA/ECHO data for educational purposes. It is not a substitute for your utility’s official Consumer Confidence Report or public notices.
System facts
- PWSID: TX0730002
- Type: Community water system (active)
- Primary source: Surface water (lakes/rivers)
- Owner type: Local government
- Wholesaler flag: No
- Phone (EPA record): 254-883-1450
- Address (EPA record): 101 FORTUNE ST, Marlin 76661
Recent violation records (indexed subset)
Showing up to 40 recent violation identities (2021+ when dated), deduplicated from SDWA_VIOLATIONS_ENFORCEMENT. Status meanings come from EPA’s data dictionary (Resolved / Addressed / Unaddressed / Archived).
| Begin | Contaminant / issue | Violation | Category | Health-based | Status | Result / MCL |
|---|---|---|---|---|---|---|
| 12/30/2021 | Lead and Copper Rule | Lead Consumer Notice | MR | No | Resolved | — / MCL TT |
| 10/01/2025 | TTHM | Maximum Contaminant Level Violation, Average | MCL | Yes | Resolved | .102 MG/L / MCL 0.080 mg/L |
| 10/01/2025 | Total Haloacetic Acids (HAA5) | Maximum Contaminant Level Violation, Average | MCL | Yes | Archived | .143 MG/L / MCL 0.060 mg/L |
| 08/25/2025 | Public Notice | Public Notification Violation for NPDWR Violation | Other | No | Unaddressed | — / MCL |
| 08/25/2025 | Public Notice | Public Notification Violation for NPDWR Violation | Other | No | Unaddressed | — / MCL |
| 08/24/2024 | Public Notice | Public Notification Violation for NPDWR Violation | Other | No | Resolved | — / MCL |
| 07/02/2025 | LEAD AND COPPER RULE REVISIONS | Notification, Known or Potential LSL | RPT | No | Unaddressed | — |
| 07/01/2025 | Total Haloacetic Acids (HAA5) | Maximum Contaminant Level Violation, Average | MCL | Yes | Resolved | .133 MG/L / MCL 0.060 mg/L |
| 07/01/2025 | Consumer Confidence Rule | Consumer Confidence Report Inadequate Reporting | Other | No | Unaddressed | — / MCL |
| 07/01/2025 | TTHM | Maximum Contaminant Level Violation, Average | MCL | Yes | Resolved | .106 MG/L / MCL 0.080 mg/L |
| 07/01/2024 | Total Haloacetic Acids (HAA5) | Maximum Contaminant Level Violation, Average | MCL | Yes | Archived | .082 MG/L / MCL 0.060 mg/L |
| 07/01/2023 | Consumer Confidence Rule | Consumer Confidence Report Inadequate Reporting | Other | No | Resolved | — / MCL |
| 07/01/2022 | Consumer Confidence Rule | Consumer Confidence Report Complete Failure to Report | Other | No | Resolved | — / MCL |
| 06/22/2026 | Public Notice | Public Notification Violation for NPDWR Violation | Other | No | Unaddressed | — / MCL |
| 06/22/2026 | Public Notice | Public Notification Violation for NPDWR Violation | Other | No | Unaddressed | — / MCL |
| 06/12/2026 | Public Notice | Public Notification Violation for NPDWR Violation | Other | No | Unaddressed | — / MCL |
| 06/12/2026 | Public Notice | Public Notification Violation for NPDWR Violation | Other | No | Unaddressed | — / MCL |
| 06/12/2026 | Public Notice | Public Notification Violation for NPDWR Violation | Other | No | Unaddressed | — / MCL |
| 06/12/2026 | Public Notice | Public Notification Violation for NPDWR Violation | Other | No | Unaddressed | — / MCL |
| 06/03/2024 | Total Haloacetic Acids (HAA5) | Failure Submit IDSE/Subpart V Plan Rpt | MR | No | Resolved | — / MCL 0.060 mg/L |
| 05/02/2026 | Public Notice | Public Notification Violation for NPDWR Violation | Other | No | Unaddressed | — / MCL |
| 04/18/2026 | Public Notice | Public Notification Violation for NPDWR Violation | Other | No | Unaddressed | — / MCL |
| 04/14/2024 | Public Notice | Public Notification Violation for NPDWR Violation | Other | No | Addressed | — / MCL |
| 04/01/2026 | Total Haloacetic Acids (HAA5) | Maximum Contaminant Level Violation, Average | MCL | Yes | Archived | .062 MG/L / MCL 0.060 mg/L |
| 04/01/2026 | Long Term 2 Enhanced Surface Water Treatment Rule | Treatment Technique (SWTR and GWR) | TT | Yes | Resolved | — / MCL |
| 04/01/2025 | TTHM | Maximum Contaminant Level Violation, Average | MCL | Yes | Resolved | .109 MG/L / MCL 0.080 mg/L |
| 04/01/2025 | Total Haloacetic Acids (HAA5) | Maximum Contaminant Level Violation, Average | MCL | Yes | Resolved | .135 MG/L / MCL 0.060 mg/L |
| 04/01/2024 | Total Haloacetic Acids (HAA5) | Maximum Contaminant Level Violation, Average | MCL | Yes | Archived | .087 MG/L / MCL 0.060 mg/L |
| 04/01/2024 | TTHM | Maximum Contaminant Level Violation, Average | MCL | Yes | Resolved | .084 MG/L / MCL 0.080 mg/L |
| 04/01/2021 | Long Term 2 Enhanced Surface Water Treatment Rule | Treatment Technique (SWTR and GWR) | TT | Yes | Resolved | — / MCL |
| 03/01/2026 | Long Term 2 Enhanced Surface Water Treatment Rule | Treatment Technique (SWTR and GWR) | TT | Yes | Resolved | — / MCL |
| 02/20/2025 | Public Notice | Public Notification Violation for NPDWR Violation | Other | No | Resolved | — / MCL |
| 02/01/2023 | Surface Water Treatment Rule | Monitoring of Treatment (SWTR-Filter) | MR | No | Resolved | — / MCL |
| 01/01/2026 | Total Haloacetic Acids (HAA5) | Maximum Contaminant Level Violation, Average | MCL | Yes | Archived | .153 MG/L / MCL 0.060 mg/L |
| 01/01/2026 | TTHM | Maximum Contaminant Level Violation, Average | MCL | Yes | Resolved | .105 MG/L / MCL 0.080 mg/L |
| 01/01/2024 | Total Haloacetic Acids (HAA5) | Maximum Contaminant Level Violation, Average | MCL | Yes | Archived | .065 MG/L / MCL 0.060 mg/L |
| 01/01/2021 | Total Haloacetic Acids (HAA5) | Maximum Contaminant Level Violation, Average | MCL | Yes | Resolved | .067 MG/L / MCL 0.060 mg/L |
| — | Unspecified | — | No | — | — |
Lead & copper rule sample highlights
Codes PB90 / CU90 in SDWIS typically represent 90th percentile lead/copper monitoring results under the Lead and Copper Rule.
Lead (PB90)
- 12/31/2024: 0 mg/L
- 12/31/2021: .0049 mg/L
- 12/31/2020: .0083 mg/L
- 12/31/2018: .00396 mg/L
- 12/31/2017: .00396 mg/L
- 12/31/2014: .0034 mg/L
- 12/31/2013: .0101 mg/L
- 12/31/2010: .014 mg/L
FAQs
What does PWSID TX0730002 mean?
A Public Water System Identification number uniquely identifies a system in EPA’s Safe Drinking Water Information System (SDWIS). Texas IDs start with TX.
How current is this page?
Systems and geography reflect the EPA SDWA quarterly snapshot used for this build. Violation rows are a filtered recent subset (generally 2021+) and capped for readability—always confirm on ECHO and your CCR.
What should I do if I see a health-based violation?
Read the dates and status. Contact the utility for context, check for public notices, and review the newest Consumer Confidence Report. For medical concerns, talk with a clinician—this site is educational only.
Do lead/copper samples mean my home is safe?
LCR samples are utility monitoring results (often 90th percentile summary codes like PB90/CU90), not a test of every tap. Home plumbing can differ. Consider a certified lab test if you have reason for concern.
Citations
- EPA SDWIS via ECHO SDWA downloads: systems, geographic areas, violations/enforcement, LCR samples — SDWA Data Download Summary
- Explore the system in EPA tools using PWSID
TX0730002— ECHO home - Learn more about standards: EPA Safe Drinking Water Act