Utility · TX0300001

CITY OF BAIRD

CITY OF BAIRD (PWSID TX0300001) is an active community water system in Texas serving about 1,534 people through roughly 977 service connections. Its primary source is listed as surface water (lakes/rivers). Cities/areas associated with this system in EPA geographic data: Baird. In recent EPA records indexed here, we found 39 violation record(s), including 11 health-based and 2 still listed as addressed/unaddressed (not fully resolved). This page summarizes public EPA SDWA/ECHO data for educational purposes. It is not a substitute for your utility’s official Consumer Confidence Report or public notices.

1,534population served
977service connections
11health-based viol.
39viol. rows indexed

System facts

  • PWSID: TX0300001
  • Type: Community water system (active)
  • Primary source: Surface water (lakes/rivers)
  • Owner type: Local government
  • Wholesaler flag: Yes
  • Phone (EPA record): 325-854-1212
  • Address (EPA record): 328 MARKET ST, Baird 79504

Service geography

Cities/areas:

Baird

Counties: Callahan

ZIPs served (EPA geo): —

Recent violation records (indexed subset)

Showing up to 40 recent violation identities (2021+ when dated), deduplicated from SDWA_VIOLATIONS_ENFORCEMENT. Status meanings come from EPA’s data dictionary (Resolved / Addressed / Unaddressed / Archived).

BeginContaminant / issueViolationCategoryHealth-basedStatusResult / MCL
12/22/2023Revised Total Coliform RuleTreatment Technique, Level 1 Assessment (RTCR)TTYesResolved—
12/21/2023Public NoticePublic Notification Violation for NPDWR ViolationOtherNoResolved— / MCL
11/27/2024TTHMFailure Submit IDSE/Subpart V Plan RptMRNoResolved— / MCL 0.080 mg/L
11/21/2022TTHMFailure Submit IDSE/Subpart V Plan RptMRNoResolved— / MCL 0.080 mg/L
10/17/2024LEAD AND COPPER RULE REVISIONSLSL ReportingRPTNoResolved—
10/17/2024LEAD AND COPPER RULE REVISIONSLSL InventoryTTYesResolved—
10/11/2024Public NoticePublic Notification Violation for NPDWR ViolationOtherNoResolved— / MCL
10/01/2025Lead and Copper RuleFollow-up Or Routine LCR Tap M/RMRNoUnaddressed— / MCL TT
10/01/2024TTHMMaximum Contaminant Level Violation, AverageMCLYesResolved.129 MG/L / MCL 0.080 mg/L
10/01/2023TTHMMaximum Contaminant Level Violation, AverageMCLYesResolved.1 MG/L / MCL 0.080 mg/L
10/01/2022Lead and Copper RuleFollow-up Or Routine LCR Tap M/RMRNoResolved— / MCL TT
09/29/2023Lead and Copper RuleLead Consumer NoticeMRNoResolved— / MCL TT
09/06/2023TTHMFailure Submit IDSE/Subpart V Plan RptMRNoResolved— / MCL 0.080 mg/L
09/01/2025Surface Water Treatment RuleMonitoring of Treatment (SWTR-Filter)MRNoResolved— / MCL
09/01/2025Interim Enhanced Surface Water Treatment RuleMonitoring, Turbidity (Enhanced SWTR)MRNoResolved— / MCL
09/01/2021Interim Enhanced Surface Water Treatment RuleMonitoring, Turbidity (Enhanced SWTR)MRNoResolved— / MCL
08/01/2021Interim Enhanced Surface Water Treatment RuleMonitoring, Turbidity (Enhanced SWTR)MRNoResolved— / MCL
08/01/2021Interim Enhanced Surface Water Treatment RuleMonitoring, Turbidity (Enhanced SWTR)MRNoResolved— / MCL
07/14/2024Public NoticePublic Notification Violation for NPDWR ViolationOtherNoResolved— / MCL
07/02/2024Consumer Confidence RuleConsumer Confidence Report Inadequate ReportingOtherNoResolved— / MCL
07/01/2025Consumer Confidence RuleConsumer Confidence Report Inadequate ReportingOtherNoUnaddressed— / MCL
07/01/2024TTHMMaximum Contaminant Level Violation, AverageMCLYesResolved.133 MG/L / MCL 0.080 mg/L
07/01/2021Consumer Confidence RuleConsumer Confidence Report Complete Failure to ReportOtherNoResolved— / MCL
06/19/2024Public NoticePublic Notification Violation for NPDWR ViolationOtherNoResolved— / MCL
06/16/2025TTHMFailure Submit IDSE/Subpart V Plan RptMRNoResolved— / MCL 0.080 mg/L
06/10/2023TTHMFailure Submit IDSE/Subpart V Plan RptMRNoResolved— / MCL 0.080 mg/L
06/01/2021Revised Total Coliform RuleMaximum Contaminant Level Violation, E. coli (RTCR)MCLYesResolved—
05/01/2026Revised Total Coliform RuleMonitoring, Routine (RTCR)MONNoArchived—
05/01/2025Public NoticePublic Notification Violation for NPDWR ViolationOtherNoResolved— / MCL
04/02/2026Public NoticePublic Notification Violation for NPDWR ViolationOtherNoResolved— / MCL
04/01/2026Revised Total Coliform RuleMonitoring, Routine (RTCR)MONNoArchived—
04/01/2025TTHMMaximum Contaminant Level Violation, AverageMCLYesResolved.086 MG/L / MCL 0.080 mg/L
04/01/2024TTHMMaximum Contaminant Level Violation, AverageMCLYesResolved.125 MG/L / MCL 0.080 mg/L
04/01/2023TTHMMaximum Contaminant Level Violation, AverageMCLYesResolved.101 MG/L / MCL 0.080 mg/L
02/18/2024Public NoticePublic Notification Violation for NPDWR ViolationOtherNoResolved— / MCL
01/01/2026Revised Total Coliform RuleMonitoring, Routine (RTCR)MONNoResolved—
01/01/2025TTHMMaximum Contaminant Level Violation, AverageMCLYesResolved.108 MG/L / MCL 0.080 mg/L
01/01/2024TTHMMaximum Contaminant Level Violation, AverageMCLYesResolved.122 MG/L / MCL 0.080 mg/L
—Unspecified—No——

Lead & copper rule sample highlights

Codes PB90 / CU90 in SDWIS typically represent 90th percentile lead/copper monitoring results under the Lead and Copper Rule.

Lead (PB90)

  • 12/31/2025: 0 mg/L
  • 12/31/2024: .00893 mg/L
  • 12/31/2023: 0 mg/L
  • 12/31/2002: .0006 mg/L
  • 12/31/1999: .0063 mg/L
  • 12/31/1996: .003 mg/L
  • 12/31/1995: .0034 mg/L
  • 12/31/1993: .0034 mg/L

Lead explainer →

Copper (CU90)

No LCR copper samples in the extracted slice.

Copper explainer →

FAQs

What does PWSID TX0300001 mean?

A Public Water System Identification number uniquely identifies a system in EPA’s Safe Drinking Water Information System (SDWIS). Texas IDs start with TX.

How current is this page?

Systems and geography reflect the EPA SDWA quarterly snapshot used for this build. Violation rows are a filtered recent subset (generally 2021+) and capped for readability—always confirm on ECHO and your CCR.

What should I do if I see a health-based violation?

Read the dates and status. Contact the utility for context, check for public notices, and review the newest Consumer Confidence Report. For medical concerns, talk with a clinician—this site is educational only.

Do lead/copper samples mean my home is safe?

LCR samples are utility monitoring results (often 90th percentile summary codes like PB90/CU90), not a test of every tap. Home plumbing can differ. Consider a certified lab test if you have reason for concern.

Citations